ADDENDUM #2 Interior
Masonry Chimney
Conversions
•
Follow the requirements and use
the equipment listed in the
illustration below to install this
appliance into an interior masonry
chimney.
•
Maximum vertical rise is 40'
•
Minimum vertical rise is 10'
•
See the chart on page 15 for
determining the correct restrictor
position.
NOTE: these restrictor positions
are based upon lab tests. The ideal
restrictor position may vary slightly.
Travis Industries
Installation Addenda
Interior Masonry Chimney
Standard Masonry Fireplace
1 0 0 - 0 1 1 4 2
The entire chimney system
must be air-tight. Make sure to
seal the flashing, clean-out,
and thimble connection, and to
inspect the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
#990 90° Elbow
Co-Axial Straight
Lengths
The entire chimney system
must be air-tight. Seal the
connector cover and inspect
the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
3 9
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit
4" Dia. Flex Line
(UL 1777 Gas Liner)
Connector with Cover
(included in #934 Masonry
Conversion Kit)
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit)
4" Dia. Flex Line
(UL 1777 Gas Liner)
Connector (included in #934
Masonry Conversion Kit)
secured and sealed to
block-off plate.
4 0 2 0 9 1 7