Do not exceed the ranges specified for environmental conditions during
use/storage.
Do not install or store the unit in the places listed below.
Do not store in places where the humidity is lower than 10% or higher than 90%.
Do not use the unit in places where the ambient temperature is lower than 0°C or higher than
40°C. (With no condensation)
Do not use in places where the humidity is lower than 10% or higher than 90%.
Do not install/store the unit in closed places such as cabinets with no clearance, places where
there is flammable or corrosive gas, places with large amounts of dust, places exposed to direct
sunlight, places exposed to shock or vibration, salty or wet places, or outdoors.
Installation or storing the unit in such a place may cause a fire.
Do not connect equipment that exceeds the output capacity of the unit.
You can use plug strip to connect additional devices, but do not connect
devices that exceed the current capacity of the plug strip.
The current protection of the unit may operate, which may stop the output.
The wiring of the plug strip heats up, which may cause a fire.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and have the cable repaired.
For repair, contact us; ____
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
Doing so may compromise the safety of devices.
Do not block the air vents (front and rear).
Doing so will cause the internal temperature to rise, which may cause the unit to fail and the bat-
tery to deteriorate.
Leave at least 5 cm of space between the front vent and the wall, and at least 10 cm of space
between the rear vent and the wall.
Do not connect devices that cannot be used with commercial power
supply.
When the unit's power switch is turned ON and an error occurs with the connected device, by-
pass operation is performed and commercial power supply is supplied as is to the connected
devices.
When installing the unit on a rack, place it on the lower shelf.
Injury may result if the unit falls.
Make sure to use the mounting screws included with the brackets.
Mounting screws other than those included may not be strong enough to support the unit, caus-
ing it to fall.
If you attach the case using long screws other than those included with the product, you may
damage the internal parts of the unit.
When using the unit in the 100V output mode, check that the output
voltage is set to 100V, and then turn ON the power switch.
Connecting a 100V device to the unit while outputting in the 200V mode may cause a failure of
the device or a fire.
The output voltage can be set with "Settings" - "In/Out Settings" - "Output Voltage" in the menu
on the LCD.
Caution
(for installation and connection)
vii