Omron BU2002RWL Instruction Manual page 32

Uninterruptible power supply (ups/200-240v model)
Table of Contents

Advertisement

(Example of connection)
<BU2002RWL/BU3002RWL>
Power supply
200 VAC
External breaker
with 250V/20A.
(double pole)
<BU5002RWL>
Power supply
200 VAC
External breaker
with 250V/35A.
(double pole)
The unit was charged before shipment, but it may have self-discharged during shipment,
resulting in a reduced backup time.
We recommend charging the unit before use.
You can perform "2-5 Checking the operation" on page 21 also before charging the battery.