2-2-1. Rackmount installation (EIA /JIS 19-inch rack/server rack)
When performing rack installation, ensure that the UPS is supported and
stabilized by using both the support angles and the table clamps that
were included.
●
When installing on a rack, make sure that the UPS is supported by the each unit individually.
●
When installing on a rack, make sure to use the support angles and table clamps included with the
product. Without the support angles, the front clamp alone cannot support the weight of the UPS.
●
The mass of each unit: BU2002RWL: Approx. 28kg
In a case where the UPS is to be mounted on a rack, place it on the lower
part of the rack.
●
Dropping it may result in injury.
Be sure to use the supplied mounting screws.
●
Use of long screws other than those supplied for case mounting may damage inside the unit.
●
Screws other than those supplied may not be strong enough to support the UPS, causing it to fall.
Items included in the 19-inch rack support angle mounting bracket set
●
Rack rail (front) L/R ........................................1 each
Rack rail (rear) L/R .........................................1 each
Unit guide rail L/R ..........................................1 each
Ear bracket L/R ..............................................1 each
Spacers .................................................................. 2
Bracket mounting screws (M4) ................ ............ 10
EIA/JIS rack fixing screws (M5) ........................... 10
EIA rack fixing nuts (M5) ...................................... 10
Rack mounting procedure
●
(1) Insert the 2 included bracket mounting screws (M4) and half-tighten them to hold the front
and rear rack rails in place. ①
There are two types of front and rear rack rails: left (L) and right (R).
Caution
BU5002RWL: Approx. 61kg
①
2 bracket fixing
screws (M4)
2002
3002
BU
RWL/BU
BU3002RWL: Approx. 33kg
5002
RWL/BU
RWL
2
10