Advertisement

K. Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping fl ue section
of the termination cap MUST be used when connecting
vent.
• 38 mm minimum overlap of fl ue telescoping section
is required.
Failure to maintain overlap may cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow the
cap location guidelines as prescribed by current local or
national codes and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require in-
stallation of a cap shield to prevent anything or anyone
from touching the hot cap.
Note: When using termination caps with factory-supplied heat
shield attached, no additional wall shield fi restop is required on
the exterior side of a combustible wall.
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
WALL SHIELD
FIRESTOP
SLIP SECTION
CAN BE EXTENDED
INNER VENT
OUTER VENT
INTERIOR
Figure 10.17 Venting through the wall
40
HEAT SHIELD
3,8 CM MIN.
OVERLAP
SHEATHING
EXTERIOR
Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. C • 3/10