Gas Supply Connection - Jøtul GF 300 BV Allagash Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Pilot Head
Orifice
Ignitor
Thermocouple
Figure 16. Pilot orifice removal and replacement.
15. Install the new regulator: Be sure the new gasket is
properly positioned and tighten screws securely.
16.Install the identification labels to the stove so that
they can be seen by any person that may be servicing
the stove.
Label A: apply to back of stove.
Label B: apply to stove's rating plate.
Small valve Label: apply to valve.
17. Reassemble the stove, apply gas to the system and
check for leaks using a soapy water solution.
NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
18.Correct gas pressure is essential for efficient and safe
operation of this appliance. Use a manometer to
check pressures as specified in the Gas Pressure
section of this manual (page 15).
19. Adjust the Air Shutter. You will need to position the
shutter to provide a gas/air mixture that will achieve
the best flame picture with your particular installa-
tion. Start with the shutter stem at the half-way
position in the slot in the bottom of the stove. See fig.
12. Pushing the stem back will restrict air, while
pushing it forward will open the shutter and increase
air. With some experimentation, you will find the
shutter position that works best for your installation.
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE
INSIDE BACK COVER OF THIS MANUAL WHEN LIGHTING
YOUR STOVE.
Thermopile
Retainer
Clip
Pilot Base
Figure 17 Regulator assembly.

Gas Supply Connection

BLOWER NOTE: Install the optional blower before
connecting the gas line in order to ensure adequate
clearance between both.
The gas supply line connection is made to the left side of
the front-mounted valve. The gas supply line should be 3/
8" npt with a 1/2" diameter supply, or the appropriate size
to provide sufficient gas pressure to the valve regardless
of the input setting.
acceptable in many areas in the U.S. However, Canadian
methods vary depending on local code.
OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY
WITH THE MOST RECENT EDITION OF THE NATIONAL
FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.
union, to be installed in the supply line, and in the same
room as the appliance. This allows for the disconnection
of the stove for servicing and maintenance. See fig. 18.
sealing compounds. For propane units be sure to use
compounds that are propane resistant. Turn on gas supply
and test for gas leaks using a soapy water solution. Never
use an open flame to check for leaks.
Regulator Tower
Remove black gasket
from regulator assembly
Valve
The use of Flexible Gas Appliance Connectors is
ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE
All codes require a gas shut-off valve (gas cock) and
A T-HANDLE GAS COCK IS REQUIRED IN
MASSACHUSETTS TO COMPLY WITH CODE 248CMR.
Secure all joints tightly using appropriate tools and
13