Note: The well recovery period also occurs at the end of the watering cycle to prevent another start time or another
program cycle from starting until the reservoir has recovered.
Example 3: The irrigation supply is pumped from a reservoir fed by a self-contained well water system.
Program setup:
• Program start time: 3:00 a.m.
• Assigned Stations: 1, 2 and 3 each with a 20-minute station run time.
• PS/MV circuit: On.
• PS/MV circuit delay: 60 seconds.
• Well Recovery time: 15 minutes.
• PS/MV circuit operation during well recovery: Disabled.
Note: The well recovery period also occurs at the end of the watering cycle to prevent another start time or another
*
program cycle from starting until the reservoir has recovered.
12:30 PM
Page 39
39