Omron Powli BU1002SW Instruction Manual page 46

Uninterruptible power supply (ups/200 to 240v specifications)
Hide thumbs Also See for Powli BU1002SW:
Table of Contents

Advertisement

● Setting for whether or not to perform battery test (setting switch 3 )
... Factory setting: OFF
OFF: The battery test is automatically executed once every 4 weeks.
ON:
Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
● Auto startup mode setting (setting switch 4 ) ... Factory setting: OFF
OFF: (Mode A)
After UPS stopped, the UPS is automatically started immediately when "ON" is
detected for the AC input.
ON: (Mode B)
After UPS stopped, the UPS is automatically started in the AC input's "OFF to ON"
timing that is detected.
(Defi nition of AC input OFF: When AC input is OFF for 1 second or more)
* Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting switch
2 ) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup stop
signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the
unit operates in Mode A regardless of this setting.