Outdoor Unit (Ras-24Ua-E3, Ras-24Uax3, Ras-24Uax3-T); Outdoor Unit (Ras-24Ua-Ar3); Outdoor Unit (Ras-18Uax3, Ras-18Ua-E3) - Toshiba RAS-24UKHP-E3 Service Manual

Toshiba split wall type air conditioner service manual
Table of Contents

Advertisement

4-5. Outdoor Unit (RAS-24UA-E3, RAS-24UAX3, RAS-24UAX3-T)

No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Magnetic contactor

4-6. Outdoor Unit (RAS-24UA-AR3)

No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Magnetic contactor
5

4-7. Outdoor Unit (RAS-18UAX3, RAS-18UA-E3)

No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Magnetic contactor
Type
Output (Rated) 2200 W, 2 poles, 1 phase, 220 − 240 V, 50 Hz
2JS386D5BB02
Winding resistance (Ω )
(at 20 °C)
Output (Rated) 65 W, 6 poles, 1 phase, 220 − 240 V, 50 Hz
Winding resistance (Ω )
KFG6-71SB5P-T
(at 20 °C)
451355KQ
AC 450 V, 3.5µF
AC 440 V, 60µF
DS441606CPNE
220 − 240 V, 50 Hz
CLK-35J
Type
Output (Rated) 2200 W, 2 poles, 1 phase, 220 − 240 V, 50 Hz
2JS386D5BB02
Winding resistance (Ω )
(at 20 °C)
Output (Rated) 65 W, 6 poles, 1 phase, 220 − 240 V, 50 Hz
Winding resistance (Ω )
MMF-230-65I
(at 20 °C)
AC 450 V, 3.5µF
451355KQ
AC 420 V, 60µF
SK42CMP60U1-S
220 − 240 V, 50 Hz
CLK-35J
Type
Output (Rated) 1500 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
2JS350D5DA02
Winding resistance (Ω)
(at 20°C)
Output (Rated) 42 W, 6 poles, 1 phase, 220 – 240 V, 50 Hz
HF-240-42B-1
Winding resistance (Ω)
(at 20°C)
451205KQ
AC 450 V, 2µF
371456JCR
AC 370 V, 45µF
CLK-26J
220 – 240 V, 50 Hz
− 18 −
FILE NO. SVM-04008
Specifications
C-R
0.886
Red-Black
White-Black
64.4
Specifications
C-R
0.886
Red-Black
White-Black
71.2
Specifications
C-R
0.981
Red-Black
White-Black
176.2
C-S
1.979
127.4
C-S
1.979
139.0
C-S
2.845
290.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents