7-1. Outline of Air Conditioner Control

This is a fixed capacity type air conditioner, which uses
a DC motor for an indoor fan. The DC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit controller receives operation
commands from the indoor unit, and operates the
outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the outdoor heat
exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only

7. OPERATION DESCRIPTION

7-1-1. Louver control
(1) Vertical air flow louver
(2) Swing
7-1-2. Indoor fan control (DC Fan motor)
(1) The indoor fan is operated by the stepless speed
(2) For air flow level, speed of the indoor fan motor is
Operations according
to the commands
from the indoor unit
– 30 –
FILE NO. SVM-04008
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
change DC motor.
controlled in five steps (LOW, LOW
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
Table 7-1-1
RAS-24UKHP-E3
MODEL
Motor speed Air flow level Motor speed Air flow level
(rpm)
Cooling
HIGH
1350
and
MED
1150
Fan only
LOW
1000
HIGH
1350
Heating
MED
1200
LOW
1050
RAS-24UKP-E3
RAS-24UKPX3
MODEL
RAS-24UKP-AR3
RAS-24UKPX3-T
Cooling
HIGH
1350
and
MED
1150
Fan only
LOW
1000
MODEL
RAS-18UKPX3-T2
Cooling
HIGH
1350
and
MED
1050
Fan only
LOW
900
+
LOW
=
+
MED
=
+
, MED, MED
RAS-18UKHP-E3
(m
3
/h)
(rpm)
(m
3
/h)
950
1150
750
750
1050
650
600
900
530
950
1200
800
800
1100
700
650
950
570
RAS-18UKP-E3
RAS-18UKPX3
RAS-18UKP-AR3
950
1150
750
750
1050
650
600
900
530
950
650
530
LOW+MED
2
MED+HIGH
2
+