Refrigeration Cycle Diagram; Ras-24Ukhp-E3 / Ras-24Uah-E3 - Toshiba RAS-24UKHP-E3 Service Manual

Toshiba split wall type air conditioner service manual
Table of Contents

Advertisement

5-1. RAS-24UKHP-E3 / RAS-24UAH-E3

Cooling
0.39 m
Heating
(Connecting pipe)
∅15.88
O.D.:15.88 mm
P
Packed valve
(∅15.88)
Gas container connection (Reinstall etc.)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50 Hz
Standard
Heating
High temperature
Low temperature*1
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.

5. REFRIGERATION CYCLE DIAGRAM

Indoor unit
Evaporator
Cross flow fan
PH310X3-4MM
Accumulator
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
exchanger interchanging
(MPaG)
0.4
0.5 ~ 0.7
0.3
0.4
0.5
0.3
T
Capillary tube
∅ 0.8x500 l
Refrigerant
R22 1.63 kg
Mark (
) means check points of Gas Leak
Surface temp. of heat
pipe T (°C)
43.0
52.0 ~ 59.0
36.0
11.0
12.0
1.0
– 20 –
FILE NO. SVM-04008
0.49 m
(Connecting pipe)
∅6.35
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅ 2.4x1400 l
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
Outdoor
High
20/–
Low
27/–
High
20/–
–10/–10
High
27/19
High
32/23
Low
21/15
7/6
24/18
35/24
43/26
21/15

Hide quick links: