Communications
H Settings for Serial Communications Boards and Units
• The settings required in the Setup Area/PC Setup for Serial Communications Boards and Units are
shown in the following tables.
CS/CJ Series
• Use the following ports for CS/CJ-series Communications Boards and Units:
S Port 2 of the CS1W-SCB41 Serial Communications Board
S Port 2 of the CJ1W-SCU41 Serial Communications Unit
DM Area
Board
Port 1
Port 2
D32000
D32010
D32001
D32011
D32008
D32018
D32009
D32019
Note Use the settings marked with an asterisk in the above table.
C200HX/HG/HE and CQM1H
• Use the following ports for C200HX/HG/HE and CQM1H Communications Boards:
S Port A of the C200HW-COM06-EV1 Communications Board
S Port 2 of the CQM1H-SCB41 Serial Communications Board
Unit
Port 1
Port 2
m
m+10
15
12 to 14
08 to 11
05 to 07
04
03
02
01
00
m+1
m+11
04 to 15
00 to 03
m+8
m+18
15
00 to 14
m+9
m+19
00 to 15
Bit
Meaning
Port settings
0: Default settings
1*: User settings
Reserved
Serial communications mode
(6 Hex*: Protocol macro)
Reserved
Start bits
0*: 1 bit; 1: 1 bit (1 start bit is always
used regardless of this setting)
Data length
0: 7 bits; 1*: 8 bits
Stop bits
0: 2 bits; 1*: 1 bit
Parity
0: Yes; 1*: No
Parity
0*: Even; 1: Odd
Reserved
Baud rate (unit: bps)
0: Default (9,600); 3: 1,200; 4: 2,400; 5:
4,800; 6*: 9,600; 7: 19,200; 8: 38,400
Transmission method
0: Half duplex; 1*: Full duplex
Reserved
Maximum number of bytes in protocol
macro send/receive data: 00C8* to
03E8 (Hex)
Chapter 7
m = D30000 + 100 × unit number
g
Setting
g
860E
0006
8000
00C8
7-33