9. Extending the backup time

9-1 Connecting an additional battery unit

You can extend the backup time by connecting an additional optional battery unit to the UPS.
You can connect only one additional battery unit.
When an additional battery unit is connected, the charging time is 24 hours.
Adding BUM100S to the BU1002SW
For the BUM100S, the included battery connection cable is provided with cable clamps attached. Connect the
battery connection cable according to the instructions below.
(1) Loosen the screws and remove the battery connector covers on the rear side of the unit and battery unit.
Use the removed screws to attach the cable clamps.
(2) Connect the battery connection cable to the battery connectors on the rear side of the unit and the battery
unit. To simplify the operation, do not yet tighten the screws that hold the battery connection cable on the
cable clamp.
(3) Use screws to attach the cable clamps to the rear side of the unit and the battery unit (2 screws each).
(4) Tighten the screws that hold the battery connection cable on the cable clamps.
(5) Turn ON the overcurrent protection switch on the back of the battery unit.
(6) Connect the AC input plug of the unit to a wall outlet. The additional battery lamp on the unit's operation
panel turns ON.
See also
For information on backup time, see the backup time table in "5-2 Estimated backup time".
➛ Page 51