Buderus Logano GA124 Installation And Maintenance Instructions Manual page 41

Sealed combustion gas boiler
Hide thumbs Also See for Logano GA124:
Table of Contents

Advertisement

Placing the heating system in operation
8. Turn gas valve ON/OFF switch counterclockwise to
ON position.
9. The automatic igniter must generate sparks towards
the pilot burner. The pilot flame must appear and
then ignite the main burner. If the main burner does
not ignite, close the gas valve. Disconnect heating
system from the power supply and inform your
customer service technician or LP gas company.
10. If the main burner has ignited, the gas valve must be
checked for leaks with soap solution. If no leaks are
found, continue with step 12. If leaks have been
found, switch ON/OFF switch on gas valve
clockwise to the OFF position. Disconnect heating
system from the power supply and set the
thermostat to the lowest setting.
11. Seal leaks. Repeat steps 1 and 2 (regardless of the
control in use).
Caution:
With aquastat control continue with steps 3 and 4,
with the Logamatic 2107 continue with steps 5
and 6.
Then repeat steps 7 to 10 regardless of the control
in use.
12. Check the supply gas pressure while the boiler is
operating. The supply pressure must be between
4.7" and 10.5" W.C. for natural gas and between
11" and 13" W.C. for propane gas. Record the
measured values in the commissioning protocol in
the installation and maintenance instructions.
Natural gas
GA124
[inch W.C.]
17
23
30
Tab. 13 Manifold pressure
13. Check manifold pressure. The manifold pressure
must be set in accordance with the values in
Tab. 13. To set the manifold pressure the cover
(
Fig. 40) on the gas valve must be removed. Turn
the adjustment screw clockwise to increase the
pressure and counterclockwise to reduce the
pressure. This setting must be adjusted while the
boiler is operating.
14. Record the set value in the commissioning protocol
of the installation and maintenance instructions and
screw the safety screw (
gas valve again.
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logano GA124 special gas-fired boiler • Issue 04/2005
Propane
[inch W.C.]
3.6
8.9
3.6
9.9
3.5
9.5
Fig. 40, page 41) into the
1
5
4
Fig. 40 Gas valve
1 ON/OFF button (at ON position)
2 Screw plug for gas supply pressure measuring port
3 Safety screw for manifold pressure setting
4 Screw plug for manifold measuring port
5 Safety screw for pilot ignition pressure setting
9
2
3
41