Buderus Logano GA124 Installation And Maintenance Instructions Manual page 28

Sealed combustion gas boiler
Hide thumbs Also See for Logano GA124:
Table of Contents

Advertisement

7
Boiler installation
7.6.3 Installation of the flue and combustion air pipe
Installation of the flue pipe (
Install condensation trap.
USER NOTE
A condensation trap must always be
installed at the flue vent.
Position silicone strip approx. 1/4" wide on the boiler
intake (500 ° F-resistant silicone, use G. E. 106 or
similar).
Attach condensation trap to boiler connection (see
arrow) and secure with the included hose clamp.
Place a strip of silicone around the connection point
and smooth it to form a gas-tight connection.
Installation of the combustion air pipe at the boiler
Proceed as described above for the flue pipe to install
the combustion air pipe. A condensation trap is not
installed on the combustion air line.
28
Installation and maintenance instructions Logano GA124 special gas-fired boiler • Issue 04/2005
Fig. 27) at the boiler
2
1
Fig. 26 Condensation trap
1 Silicone strip
2 Silicone strip
3 Hose clamp
4 Condensation trap
1 2
Fig. 27 Back view
1 Combustion air line connection
2 Flue gas line
We reserve the right to make any changes due to technical modifications.