Honeywell UDC2500 Product Manual page 77

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Function Prompt
Lower Display
English
Numeric
Code
RSPSRC
804
SP TRK
805
PWR UP
806
4/07
Selection or Range of Setting
Upper Display
English
Numeric
TWO
NONE
INP2
NONE
PROC
RSP
MAN
ALSP
UDC2500 Universal Digital Controller Product Manual
Code
1
TWO LOCAL SETPOINTS—This selection
lets you switch between two local setpoints
using the SETPOINT SELECT key.
REMOTE SETPOINT SOURCE— This
selection lets you switch between the local
and remote setpoints using the
SETPOINT SELECT key.
NONE—No remote setpoint.
0
INPUT 2—Remote Setpoint is Input 2.
1
SETPOINT TRACKING—The local setpoint
can be configured to track either PV or RSP
as listed below. Not configurable when Auto
Bias is set.
ATTENTION For selections other than
NONE, LSP is stored in nonvolatile memory
only when there is a mode change; i.e.,
when switching from RSP to LSP or from
Manual to Automatic. If power is lost, then
the current LSP value is also lost.
NO TRACKING—If local setpoint tracking is
0
not configured, the LSP will not be altered
when transfer from RSP to LSP is made.
PROCESS VARIABLE (PV)—Local setpoint
1
tracks the PV when in manual.
RSP—Local setpoint tracks remote setpoint
2
when in automatic. When the controller
transfers out of remote setpoint, the last
value of the remote setpoint (RSP) is
inserted into the local setpoint.
POWER UP CONTROLLER MODE
RECALL—This selection determines which
mode and setpoint the controller will use
when the controller restarts after a power
loss.
0
MANUAL, LSP—At power-up, the controller
will use manual mode with the local setpoint
displayed.
1
AUTOMATIC MODE, LAST LSP—At power-
up, the controller will use automatic mode
with the last local setpoint used before power
down displayed.
Configuration
Parameter
Definition
63