Function Prompt
Lower Display
English
Numeric
Code
FREQ
1203
DISPLY
1205
LWRDSP
1204
LNGUAG
1206
TCDIAG
1207
4/07
Selection or Range of Setting
Upper Display
English
Numeric
60
50
SP
PRY
PRN
ENAB
DIS
ENGL
FREN
GERM
SPAN
ITAL
NUMB
ENAB
DIS
UDC2500 Universal Digital Controller Product Manual
Code
POWER LINE FREQUENCY—Select
whether your controller is operating at 50 or
60 Hertz.
0
ATTENTION For controllers powered by
1
+24 Vdc, this configuration should be set to
the AC line frequency used to produce the
+24 Vdc supply.
Incorrect setting of this parameter may cause
normal mode noise problems in the input
readings.
DEFAULT DISPLAY—For single display
units, only. This setting selects the default
parameter shown on the upper display.
Pressing the LOWER DISPLAY key will
cycle through all applicable values. One
minute after the last press of the display key,
the display will revert to the display
configured here.
SETPOINT—Active Setpoint
0
PV-YES—Process Variable with lower
1
display prompt.
PV-NO—Process Variable with no lower
2
display prompt.
LOWER DISPLY—For dual display units,
only. Select whether the unit uses single or
dual display.
0
ENAB—Enable Dual Display
1
DIS—Disable Dual Display (Single Display
Only)
LANGUAGE—This selection designates the
prompt language.
0
ENGLISH
1
FRENCH
2
GERMAN
3
SPANISH
4
ITALIAN
5
NUMERIC
THERMOCOUPLE DIAGNOSTICS—Enable
or disable Thermocouple diagnostic
messages.
ENAB—Enable Diagnostic Messages
0
DIS—Disable Diagnostic Messages
1
Configuration
Parameter
Definition
83