Honeywell UDC2500 Product Manual page 70

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration
Function Prompt
Lower Display
English
Numeric
Code
XMITR1
602
IN1 HI
603
56
Selection or Range of Setting
Upper Display
English
Numeric
B
E H
E L
J H
J M
J L
K H
K M
K L
NNMH
NNML
NICH
NICL
R
S
T H
T L
W H
W L
100H
100L
200
500
RADH
RADI
LIN
SrT
−999 to 9999
floating in
engineering units
UDC2500 Universal Digital Controller Product Manual
Code
TRANSMITTER CHARACTERIZATION—
0
This selection lets you instruct the controller
1
to characterize a linear input to represent a
2
non-linear one. If characterization is
3
performed by the transmitter itself, then
4
select LIN (Linear).
5
6
ATTENTION Prompt only appears when a
7
linear actuation is selected at prompt IN1
8
TYPE.
9
FOR EXAMPLE:
10
If input 1 is a 4 to 20 mA signal, but the
11
signal represents a type K H thermocouple,
12
then configure K H and the controller will
13
characterize the 4 to 20 mA signal so that it
14
is treated as a type K thermocouple input
15
(high range).
16
17
Parameter definitions are the same as in IN1
18
TYPE.
19
20
21
22
23
24
25
26
INPUT 1 HIGH RANGE VALUE in
engineering units is displayed for all inputs
but can only be configured for linear or
square root transmitter characterization.
Scale the #1 input signal to the display value
you want for 100 %.
EXAMPLE:
Process Variable = Flow
Range of Flow = 0 to 250 Liters/Minute
Actuation (Input 1) = 4 to 20 mA
Characterization (XMITTER) = LINEAR
Set IN1 HI display value to 250
Set IN1 LO display value to 0
Then 20 mA = 250 Liters/Minute
and 4 mA = 0 Liters/Minute
ATTENTION The control setpoint will be
limited by the range of units selected here.
Parameter
Definition
4/07