Honeywell UDC2500 Product Manual page 94

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration
Function Prompt
Lower Display
English
Numeric
Code
A2S1HL
1109
A2S1EV
1109
A2S2TY
1110
A2S2VA
1111
A2S1HL
1112
A2S1EV
1112
ALHYST
1113
80
Selection or Range of Setting
Upper Display
English
Numeric
HIGH
LOW
BEGIN
END
Value in
engineering units
HIGH
LOW
BEGIN
END
0.0 to 100.0 % of
span or full output
as appropriate
UDC2500 Universal Digital Controller Product Manual
Code
ALARM 2 SETPOINT 1 STATE—Same as
0
A1S1HL.
1
ALARM 2 SEGMENT EVENT 1—Same as
0
A1S1EV.
1
ALARM 2 SETPOINT 2 TYPE—Select what
you want Setpoint 2 of Alarm 2 to represent.
The selections are the same as A1S1TYPE.
ATTENTION Not applicable with Relay
Duplex unless using Dual Relay PWA.
ALARM 2 SETPOINT 2 VALUE—This is the
value at which you want the alarm type
chosen in prompt A2S2TYPE to actuate.
The details are the same as A1S1 VAL.
ALARM 2 SETPOINT 1 STATE—Same as
0
A1S1HL.
1
ALARM 2 SEGMENT EVENT 2—Same as
0
A1S1EV.
1
ALARM HYSTERESIS—A single adjustable
hysteresis is provided on alarms such that
when the alarm is OFF it activates at exactly
the alarm setpoint; when the alarm is ON, it
will not deactivate until the variable is 0.0 %
to 100 % away from the alarm setpoint.
Configure the hysteresis of the alarms based
on INPUT signals as a % of input range
span.
Configure the hysteresis of the alarm based
on OUTPUT signals as a % of the full scale
output range.
Parameter
Definition
4/07