Honeywell UDC2500 Product Manual page 86

Honeywell universal digital controller product manual
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration
Function Prompt
Lower Display
English
Numeric
Code
DI1COM
906
DIGIN2
907
DI2COM
908
72
Selection or Range of Setting
Upper Display
English
Numeric
DIS
+PD2
+DIR
+SP2
+SP1
+RUN
Same selections as
for Digital Input 1
Same selections as
Digital Input 1
Combinations
UDC2500 Universal Digital Controller Product Manual
Code
automatically restart at the initial Setpoint
value.
If power to the unit is lost while while a SP
Ramp or Program was running, then if the
contact is closed at power up, the unit will
automatically restart the SP Ramp or
Program at the captured Setpoint value.
DIGITAL INPUT 1 COMBINATION
SELECTIONS —This selection allows the
specified function to occur in addition to the
one chosen for DIG IN 1.
DISABLE—Disables combination function.
0
PLUS PID2—Contact closure selects PID
1
Set 2.
PLUS DIRECT ACTION—Contact closure
2
selects direct controller action.
PLUS SETPOINT 2—Contact closure puts
3
the controller into setpoint 2.
PLUS SETPOINT 1—Contact closure puts
4
the controller into setpoint 1.
5
PLUS RUN SETPOINT
PROGRAM/RAMP—Contact closure starts
SP Program/Ramp if enabled.
DIGITAL INPUT 2 SELECTIONS
DIGITAL INPUT 2 COMBINATIONS
Parameter
Definition
4/07