AC RECEPTACLE SELECTION
The generator has separate main ower producing circuits. These two
circuits supply equal power
to di f? erent receptacles shown.
Main power circuit
Main Circuit I
Main Circuit II
Receptacles powered
by each main circuit
1,4 and 6
2,3,5 and 7
Power distribution
1
+
4+ 6=39.6A rated.
2+3+5+7=39.6A rated.
*
The table shows the specifications when the 120/240V locking plug
receptacle is used for 120V.
@
120V 20A (20A Max. for
pair)
@
120V 20A (20A Max. for pair)
@ I
120V 30A
@
S@
12OV124OV 30A
@ &@
12OVl24OV 50A (43.8A Max.)
Example:
Receptacle 2 has a 17A load connected to it. Receptacle 3 has a 28A
load connected to it. Both receptacles are powered by main power
circuit II. The equation tells us that the total power draw on circuit
II is
45A. This is a substantial overload of this circuit. To eliminate the
excess power draw on circuit II, the load from receptacle 2 should be
switched to receptacle 1. Now circuit I is powering the 17A load (less
than 39.6A) and circuit II is powering a 28A load (less than 39.6A).