AC Receptacle Selection
The generator has two separate main power producing circuits. These two
circuits supply equal power to receptacles shown when the voltage
selector switch is in the 120/240 V position.
When two or more receptacles are used; prevent overloading by dividing
the load between the two power circuits.
The chart below shows the rated load in amperes that can be connected
to each receptacle to balance the generator.
The total rated ampere draw is 37.5A.
Main power circuit
Receptacles powered
Power distribution
by each main circuit
Main Circuit I
I
1,3,5 and 6
1+3+5+6=18.8A max.
Main Circuit II
2,4 and 7
2+4+7=18.8A max.
l
The table shows the specifications when the 120/24OV Twist Lock
Receptacle is used for 12OV.
Example:
Receptacle 3 has a 10 A load connected to it. Receptacle 5 has a 15A load
connected to it. Both receptacles are powered by main power circuit I. The
equation tells us that the total power draw on Circuit I is 25A. This is a
substantial overload of this circuit. To eliminate the excess power draw on
circuit I, the load from receptacle 5 should be switched to receptacle 2.
Now circuit I is powering the 1 OA load (less than 18.8A) and circuit II is
powering the 15A load (less than 18.8A).
@
120V30A
@
120V20A
@
120V20A
@
120V20A
@
120V20A
@&@
1201240 V 20 A