AC Receptacle
Selection
The generator
has two separate main power
These two circuits supply equal power to di R
reducing circuits.
shown.
erent receptacles
Main Circuit
II
--
'The table shows the specifications
when the 120/24OV locking
plug receptacle is used for 120V.
Example:
Receptacle
3 has a 10A load connected
to it. Receptacle
4 has a
15A load connected
to it. Both receptacles are powered
by main
power circuit II. The equation tells us that the total power draw on
circuit II is 25A. This is a substantial
overload
of this circuit. To
eliminate
the excess power
draw on circuit II, the load from
receptacle 3 should be switched to receptacle 2. Now circuit I is
powering the IOA load (less than 20.8A) and circuit II is powering
a 15A load (less than 20.8A).
18