AC RECEPTACLE SELECTION

The generator has separate main power producing circuits. These two
circuits supply equal power to different receptacles shown.
Main power circuit
Main Circuit I
Main Circuit II
The table shows the specifications when the 120/240V locking plug
receptacle is used for 120V.
Example:
Receptacle 2 has a 17A load connected to it. Receptacle 3 has a 28A
load connected to it. Both receptacles are powered by main power
circuit II. The equation tells us that the total power draw on circuit II is
45A. This is a substantial overload of this circuit. To eliminate the
excess power draw on circuit II, the load from receptacle 2 should be
switched to receptacle 1. Now circuit I is powering the 17A load (less
than 39.6A) and circuit II is powering a 28A load (less than 39.6A).
Receptacles powered
by each main circuit
1, 4 and 6
2, 3, 5 and 7
Power distribution
1 4 6=39.6A rated.
+ +
2 3 5 7=39.6A rated.
+ + +
120V 20A (20A Max. for pair)
120V 20A (20A Max. for pair)
120V 30A
120V/240V 30A
120V/240V 50A (43.8A Max.)