Set Temperature Rise; Gas Rate Cu Ft/Hr - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

Series 180 4-vvay mumtipoise dkect-vent variabme-capacity condensing gas furnace
Table of Contents

Advertisement

EXAMPLE:
I00,000
BTUH HIGH-HEAT
tNPUT FURNACE
INSTALLED
AT 4300 FT.
Derate
Furnace Input Rate
Furnace
Input Rate
X
Multiplier
=
at Installation
at Sea Leve_
Factor
Altitude
t00,000
X
0.91
=
91,000
(ANADA
At installation
altitudes
from 2000 to 4500 fi, this furnace
must be derated
5 percent
by an authorized
Gas (onversion
Station
or Dealer
To
detem_ine
correct
input
rate
for
altitude.,
see example
above and use 0.95 as derate
multi-
plier factor.
b. Reinstall
burner
box cover.
NOTE:
Clocking
gas input rate MUST
ahvays be performed
with
the burner
box coxer INSTALLED
c (hock
that
gas valve
adjustn_ent
caps
are in place
for
proper
input to be clocked.
d. Obtain
average
heat
value
(at
altitude)
fi'om
local
gas
supplier.
NOTE:
Be sure heating
value
of gas
used
for calculations
is
correct
_br your
altitude.
Consult
local
gas
utility
for altitude
adjustment
of gas heating
value.
e. Check and verif}_" orifice size in furnace. NEVER
ASSUME
THE ORIFI(E
SIZE.
ALWAYS
CHECK
AND VERIFY.
£ Turn off all other gas appliances
and pilots
g. Move
setup switch
SWI-2
to ON position.
(See Fig
32)
This keeps
fl/rnace
locked
in low-heat
operation.
h. Jumper
R to W/W1
i. Let fi/mace
run for 3 minutes
in low-heat
operation.
j. Measure
time (in sec) for gas meter
to complete
1 revolu-
tion. Note
reading.
k. Refer
to Table
13 tbr cubic R of gas per hr.
1. Multiply
gas rate cu ftihr by heating
value (Bmicu
ft).
m. Move
setup switch
SWI-2
to OFF position
and jumper
R
and WiWI
and W2 them_ostat
connections.
(See Fig. 32.)
This keeps/:t_mace
locked
in high-heat
operation.
Repeat
items
i through
1 tbr high-heat
operation.
EXAMPLE:
(High-heat
operation
at 0
2000 fl altitude)
Furnace
input from rating
plate
is 100,000
Bmh
Btu heating
input
Bmicu
fl X cu ftihr
Heating
value of gas
975 Bmicu
ft
Time for 1 revolution
of 2-cu fl dial
70 sec
Gas rate
103 cu ftihr ([?om Table
13)
Btu heating
input
103 X 975
100,425
Bmh
In tl-ds
example,
the orifice
size and manifold
pressure
adjustment
is within
_+2 percent
of the furnace
input rate
NOTE:
Measured
gas inputs
(high heat and tow heat) must
be
within
_+2 percent
of d_mt stated
on furnace
rating
plate
when
installed
at sea level or derated
per that stated above when installed
at higher
altitudes
n. Remove
jumper
across
R, WiWl,
and
W2
thermostat
connections
to terminate
call for heat
49
Table 13--Gas
Rate Cu Ft/Hr
SECONDS
SIZE
OF TEST
DIAL
SECONDS
SIZE
OF TEST
DIAL
FOR
1
1
2
5
FOR
1
1
2
5
REVOLUTION
cu fl
cu R
cu fl
REVOLUTION
cu fl
cuff
cu
10
380
720
1800
50
72
144
350
11
327
655
1636
51
71
141
355
12
300
600
1500
52
69
138
346
13
277
555
1385
53
68
136
340
14
257
514
1286
54
67
133
333
15
240
480
1200
55
65
131
327
18
225
450
1125
58
64
129
321
17
212
424
1059
57
63
126
316
18
200
400
1000
58
62
124
310
19
189
379
947
59
61
122
305
20
180
360
900
60
60
120
300
21
171
343
857
82
58
116
290
22
164
327
818
84
56
112
281
23
157
313
783
88
54
109
273
24
150
300
750
68
53
106
265
25
144
288
720
70
51
103
257
28
138
277
692
72
50
100
250
27
133
267
667
74
48
97
243
28
129
257
643
78
47
95
237
29
124
248
621
78
46
92
231
30
120
240
600
80
45
90
225
31
116
232
581
82
44
88
220
32
113
225
563
84
43
86
214
33
109
218
545
88
42
84
209
34
106
212
529
88
41
82
205
35
103
206
514
90
40
80
200
38
100
200
500
92
39
78
196
37
97
195
486
94
38
76
192
38
95
189
474
98
38
75
188
39
92
185
462
98
37
74
184
40
90
180
450
100
36
72
180
41
88
176
439
102
35
71
178
42
86
172
429
104
35
69
173
43
84
167
419
106
34
68
170
44
82
164
409
108
33
67
167
45
80
160
400
110
33
65
164
46
78
157
391
112
32
84
161
47
76
153
383
116
31
62
155
48
75
150
375
120
30
60
150
49
73
147
367
SET TEMPERATL
RE RISE
UNIT
DAMAGE
HAZARD
Failure
to %llow
this caution
may result
in overheating
the
heat exchangers
or condensing
flue gases in heat exchanger
areas not designed
for condensate
Temperature
rise
must
be
within
limits
specified
on unit
rating plate. Operation
is within a few degrees
of mi@oint
of
rise range
when
setup switch
SWI-4
is OFF
Furnace
must
operate
within
ranges
of temperature
rise specified
on the furnace
rating
plate.
Determine
air temperature
rise
as
follows:
1
Place them_ometers
in return and supply ducts as near furnace
as possible.
Be sure them_ometers
do not see heat exchanger
so that radiant
heat does not af_)ct readings
This practice
is
particularly
important
with straight-run
ducts.
2
When tlaern_ometer
readings
stabilize,
subtract
return-air
tem-
perature
from
supply-air
temperature
to determine
air tem-
perature
rise.
NOTE:
Temperature
rise can be detem_ined
fbr low-heat
opera-
tion by placing
setup
switch
SWl-2
on furnace
control
in ON
position
For high-heat
operation,
place
setup
switch
SW1-2
in
OFF position
and jm_aper
R-W2
on fm'nace
control
DO NOT
forget
to return
setup switch
to OFF position
and remove
R-W2
jumper
upon
completion
of testing.
(See Fig. 32 for switch
and
terminal
location.)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents