Set Temperature Rise - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

121 series
Table of Contents

Advertisement

Table 12—Gas Rate Cu Ft/Hr
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
DO NOT redrill orifices. Improper drilling (burrs, out-of-
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of burners and heat exchangers, causing
failures.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check the orifice hole with a numbered drill bit of
the correct size. Never redrill an orifice. A burr-free and squarely
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
BURNER
ORIFICE
A93059
aligned orifice hole is essential for proper flame characteristics.
g. Remove jumper R-W2 after high-heat adjustment.
h. Replace burner enclosure front and measure adjusted gas
input rate using method outlined in item 2.
i. Replace caps that conceal gas valve regulator adjustment
screws.
Be sure burner enclosure front is in place after adjustments
have been made.
j. Look through sight glass in burner enclosure and check
burner flame. The burner flame should be clear blue, almost
transparent. (See Fig. 47.)
BURNER FLAME
MANIFOLD
Fig. 47—Burner Flame

SET TEMPERATURE RISE

Temperature rise must be within limits specified on unit
rating plate. Recommended operation is at midpoint of rise or
above. Failure to follow this caution may result in condensing
or overheating the heat exchangers.
Furnace must operate within range of temperature rise specified on
the unit rating plate. Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace
as possible. Be sure thermometers do not see heat exchanger
so that radiant heat does not affect readings. This practice is
particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air tem-
perature from supply-air temperature to determine air tem-
perature rise.
NOTE: Temperature rise can be determined for low-fire opera-
tion by placing setup switch SW-2 on control center in the ON
position. For high-heat operation, place setup switch SW-2 in the
OFF position and jumper R-W2 on control center. DO NOT forget
to return setup switch to OFF position and remove R-W2 jumper
upon completion of testing. (See Fig. 25 for switch and terminal
location.)
3. This furnace is capable of automatically providing the proper
airflow to maintain the temperature rise within the range
specified on the unit rating plate. If the temperature rise is
outside this range, proceed as follows:
a. Check gas input for low- and high-heat operation.
b. Check derate for altitude if applicable.
37
BURNER
A89020

Advertisement

Table of Contents
loading

Table of Contents