Power Products Home Generator
Installation
Manual
General
Location
Guidelines
• Install the unit outdoors
ONLY.
NO MODIFICATIONS
WILL ALLOW
INSIDE INSTALLATION!
• Place the unit in a prepared location that is fiat and has
provisions for water drainage.
• Install the unit where air inlet and outlet openings will
not become obstructed
by leaves, grass, snow, etc. If
prevailing winds will cause blowing or drifting, you may
need to construct
a windbreak
to protect
the unit.
• In locations where strong winds blow from one
direction, face the generator
air inlet openings into the
prevailing winds, if possible.
• Install the generator
as close as possible to the
Automatic
Power Transfer System to reduce the length
of wiring and conduit.
• Install the generator
as close as possible to the fuel
supply to reduce length of pipes.
_
AUTION!
Laws or local codes may regulate the
distance to the fuel supply.
The Home Standby Generator
is shipped already attached
to its mounting pad. Unless mandated by local code, no
concrete slab is required.
If mandated by local code, detach the unit from its supplied
base. Construct
a concrete slab at least 3 inches thick and
6 inches longer and wider than the unit.Attach
unit to slab
with I/4" diameter (minimum)
masonry anchor bolts long
enough to retain the unit. Use the mounting pad holes as
anchor bolt Iocators.
Fuel and Electrical
Inlet
Dimensions
Figure 2, below, depicts the location of the fuel piping
connector.Also
shown is the recommended
location for
punching holes for attaching the power conduit.
Lifting
the Generator
The generator
weighs more than 375 pounds. Proper tools,
equipment
and qualified personnel should be used in all
phases of handling and moving the generator.
CAUTION!
DO NOT lift unit by roof as damage to
generator will occur.
Two 48" lengths of I" O.D. pipe (supplied by the installer)
are required to lift the generator
manually. Insert pipes
through the lifting holes located near the unit's base, as
shown in Figure 3 (next page).
_
AUTION!
The unit may shift on the lifting pipes
during movement, which may cause injury.
Recommended
Conduit Attachment
Area
p .........
,i
..... J
©
Fuel Piping
Connector
I©1
--......
©
-'
4.5"
13.5"
I
5