Power Products Home Generator
Installation
Manual
WERPRODUCTS
Generator
AC Connection
System
A single-phase, three-wire
AC connection
system is used in
the Home Standby Generator.The
stator assembly consists
of a pair of stationary windings with two leads brought out
of each winding.The
junction
of leads 22 and 33 forms the
neutral lead, as shown schematically and as wiring diagram
in Figure 10.A complete
schematic and wiring diagram can
be found in the owner's manual.
NOTE:
Neutral
is not bonded to ground at generator.
_,K_
II[0] . ..........
_TiV-,e]
[o_l'_
--33
33
22
o_
I
44
I__
Neutral
["
120V
Circuit
Breaker
--II
----o_o
44-----o
o
120V
240V
]
t
Circuit I
Breaker
I
44
7 Neutral
I
0
o
w
To Earth Ground
To Transfer Switch
Grounding
the System
Installer-supplied
minimum 8 AWG stranded copper wire is
connected to the generator housing GND lug and routed
through conduit to the Automatic
Transfer Switch's GND
bus. Continue the 8 AWG wire through conduit to the main
distribution
panel ground bus.
Utility
Control
Circuit
Connection
Control
circuit interconnections
consist of "Utility"
leads.
These two leads must be routed in conduit. Control
lead
functions
are
briefly
described
as
follows:
• "Utility
I" and "Utility
2" deliver utility power to the
generator's
circuit
board, charge the battery and when
utility is lost the generator
will start.
Using installer-supplied
minimum 300V, 14 AWG stranded
copper
wire,
connect each
control
circuit
terminal
in the
generator
to
the
Automatic
Transfer
Switch.
Fault
Detection
System
The light on the control
panel is referred to as the
Diagnostic LED. It will turn on and off in a series of blinks if
certain faults are detected in the HSG.An extra LED and
mounting plate is supplied so that it can be installed at a
convenient indoor location.The
owner will use it to
observe the status of the HSG. Consult with the owner for
a convienant location.
To install the remote
LED panel:
• Apply the supplied decal to the supplied mounting plate.
• Push the LED through the mounting plate from the front
until it snaps in place.
• Using minimum
18 AWG wire, connect the remote LED
to the generator
control
board using supplied pin
connectors.
Use wire nuts to attach wire to LED leads.
• Attach mounting plate to installer-supplied electrical box.
Refer to the section "Fault Detection
System" in the
Owner's
Manual for operation.
II

Hide quick links:

Advertisement

Table of Contents