Fuel Comparison
Chart
lal?q] _ 4'E'l,_.]dl,.[,]i _[IR'_
Physical Properties
Normal Atmospheric
State
Boiling Point (in °F):
Initial
End
Heating Value:
BTU per gallon (Net LHV*)
BTU per Gallon (Gross *_*)
Cubic Feet (Gas)
Density***
Weight t
Octane Number:
Research
Motor
Butane
Gas
32
32
94,670
102,032
3,264
31.26
4.81
Propane
Gas
-44
-44
83,340
91,547
2,516
36.39
4.24
Natural
Gas
Gas
-259
-259
63,310
1,000
57.75
2.65
94
II0+
II0+
90
97
*
LHV (Low HeatValue)
is the more realistic rating.
**
Gross HeatValue
does not consider
heat lost in the form of water during combustion.
***
Density
is given in "Cubic
Feet of Gas per Gallon of Liquid".
Weight is given in "Pounds per Gallon of Liquid".
Size of Propane
Tank Required
at Various
Temperatures
When
Kept at Least
Half Full
Given the gas withdrawal
rate and the lowest average winter
temperature,
an installer can specify the required LP storage
tank size:
Withdrawal
Rate
32°F
20°F
I 0°F
0°F
- I 0°F
-30°F
-40°F
50 CFH
115
115
115
250
250
400
600
100 CFH
250
250
250
400
500
1000
1500
150 CFH
300
400
500
500
1000
1500
2500
200 CFH
400
500
750
1000
1200
2000
2500
300 CFH
750
1000
1500
2000
2500
4000
5000