Shrouds; Hht Shrouds; Field Constructed Shrouds - Heatilator EDV3633 Owner's Manual

Direct vent gas appliance
Hide thumbs Also See for Heatilator EDV3633:
Table of Contents

Advertisement

11

Shrouds

A. HHT Shrouds
You may install a shroud with this fireplace. See Section 17.D. for a list of UL Listed shrouds. Follow the instructions
included with these optional components
B. Field Constructed Shrouds
WARNING! Risk of Fire! Shrouds must be constructed
as specified. Improper construction may overheat chase
top.
Chase top shrouds may be field constructed where permitted by regional building codes.
NOTICE: Some regional codes require an agency-Listed
shroud. Consult your local building officials.
The following field constructed shroud designs have been tested for Hearth Technologies fireplace systems and termination
caps.
The shrouds must be constructed from a minimum .08 in. (26 ga) thick aluminized steel.
The wire mesh is optional but recommended and must be .018 in. thick minimum, 1/2 in. mesh.
Open Top Shroud (may be used with DVP-TV, DVP-TVHW, SLP-TVHW)
Min.
Top Dim.
Min.
Top Dim.
Min.
Base Dim.
Figure 11.1 Open Top Shroud Dimensions
40
Min.
Base Dim.
Heatilator • Eclipse • 4049-229 Rev I • 08/09
Min. Base Dims.
in
9 x 9
48 x 48
mm
Min. Top Dims.
6 x 6
in
mm
406 x 406