Install The Ceiling Firestop - Heatilator EDV3633 Owner's Manual

Direct vent gas appliance
Hide thumbs Also See for Heatilator EDV3633:
Table of Contents

Advertisement

C. Install the Ceiling Firestop
A ceiling firestop MUST be used between
floors and attics.
Frame opening 9 in. x 9 in. (229 mm x
229 mm) whenever the vent penetrates
a ceiling/floor (see Figure 8.).
Frame the area with the same sized lumber
as used in ceiling/floor joist.
The ceiling firestop may be installed above
or below the ceiling joists when installed
with a attic insulation shield. It must be
under joists between floors that are not
insulated. Refer to Figure 8.4.
Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack
insulation around the vent. Insulation must be
kept back from the pipe to prevent overheat-
ing.
Figure 8.3
Installing Ceiling Firestop
Ceiling firestop
installed below ceiling.
Figure 8.4 Installing the Attic Shield
Heatilator • Eclipse • 4049-229 Rev I • 08/09
Attic Above
9 in. (229 mm)
9 in.
(229 mm)
Hole should measure
9 in. x 9 in.
(229 mm x 229 mm)
inside to inside
Install attic insula-
tion shields before
or after installation
of vent system.
3 fasteners
per side
Ceiling firestop
installed above ceiling.