Vent Clearances and Framing

A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling firestops
• Between wall shield firestops
• Around vent system
Failure to keep insulation or other material away from vent
pipe may cause over heating and fire.
Note: Heat shields MUST overlap by a minimum of 1 1/2 in. (38 mm).
• SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8
in. (111 mm to 194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must
be field trimmed. If wall thickness is greater than 7-5/8 in. an
extended heat shield will be required.
3 in.
(76 mm)
Drywall
1 in. (25 mm)
2 x 4 or
2 x 6
header
* When using SLP pipe, minimum clearances from the vent pipe to
combustible materials at inside wall firestops are:
Figure 8.1 Horizontal Venting Clearances To Combustible Materi-
als
0
Air space clearance to
bottom and sides of
horizontal pipe must be
at least 1 in. (25 mm)
No combustible
framing to be
located within
shaded area.
3/4 in. (19 mm)
minimum to
perpendicular
wall.
Top: 2-1/2 in. (64 mm)
Bottom: 1/2 in. (13 mm)
Sides: 1 in. (25 mm)
Heatilator • Eclipse • 4049-229 Rev I • 08/09
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield firestops. A wall shield
firestop maintains minimum clearances and prevents cold
air infiltration.
The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
A wall shield firestop must be placed on each side of
an interior wall. A minimum  /2 in. (8 mm) overlap of
attached heat shields must be maintained.
See Section 0.I. for information for regarding the
installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield firestop is only required on one side and no heat
shield is necessary.
10 in.
[254mm]
The center of the
framing hole is
1 in. [25mm] above
the center of the
horizontal vent pipe.
Framing should be
constructed of 2 X 4
lumber or heavier.
Figure 8.2 Wall Penetration
10 in.
[254mm]
Vent
framing
hole
36 1/2 in. [927 mm]
(Center of pipe)