Field Settings; Procedure; Detailed Description - Daikin EDHQ011BB6V3 Operation Manual

Altherma unit and options for air to water heat pump system
Hide thumbs Also See for EDHQ011BB6V3:
Table of Contents

Advertisement

5.
F
IELD SETTINGS
NOTICE
The default values mentioned in
page 18
are the values from factory. The actual initial
values shall be selected according to your application.
These values shall be confirmed by your installer.
CAUTION
The field settings [2] depends on the applicable
legislation.
The field settings [9] depends on the application.
Before changing these settings, the new values shall
be confirmed by the installer and/or shall be according
to the applicable legislation.
The unit shall be configured by the installer to match the installation
environment (outdoor climate, installed options, etc.) and user
demand. However, the field settings mentioned in
table" on page 18
can be modified to customer preferences. Thereto,
a number of so called field settings are available. These field settings
are accessible and programmable through the user interface on the
unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
settings table" on page
18. In this same list, we provided for 2
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
description" on page
13.

5.1. Procedure

To change one or more field settings, proceed as follows.
3
2
Press the z button for a minimum of 5 seconds to enter FIELD
1
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
Press the bgi button to select the appropriate field setting
2
first code.
Press the bgj button to select the appropriate field setting
3
second code.
Press the pfi button and pfj button to change
4
the set value of the select field setting.
Operation manual
13
"Field settings table" on

"Field settings

"Field
"Detailed
1
Save the new value by pressing the pr button.
5
6
Repeat step 2 through 4 to change other field settings as
required.
When finished, press the z button to exit FIELD SET MODE.
7
NOTICE
Changes made to a specific field setting are only stored
when the pr button is pressed. Navigating to a new field
setting code or pressing the z button will discard the
change made.
INFORMATION
Before shipping, the set values have been set as
shown under
"Field settings table" on page
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.

Detailed description

[0] User permission level
If required, certain user interface buttons can be made unavailable for
the user.
Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons pfi and pfj immediately followed by
simultaneously pressing buttons s and ba, and keeping all 4
buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].
Button
s
Quiet mode button
Weather dependent
ba
set point button
Schedule timer enable/
pr
disable button
<
Programming button
pfi
Time adjust buttons
pfj
Inspection/test
z
operation button
Unit and options for air to water heat pump system
18.
Permission level
1
2
3
operable
operable
operable
operable
operable
operable
operable
E(D/B)(H/L)Q011~016BB
4PW67905-1A – 2013.02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents