Nordyne R-410A Installation And User Manual page 16

16 seer two stage r-410a split system
Table of Contents

Advertisement

Status LED
Status LED
Description
Short Cycling
Yellow "ALERT"
Compressor is
Flash Code 3
running only
briefl y
Yellow "ALERT"
Locked Rotor
Flash Code 4
Yellow "ALERT"
Open Circuit
Flash Code 5
Open Start
Yellow "ALERT"
Circuit
Flash Code 6
Current only in
run circuit
Open run circuit
Yellow "ALERT"
Current only in
Flash Code 7
start circuit
Welded
Yellow "ALERT"
Contactor
Flash Code 8
Compressor
always runs
Low Voltage
Yellow "ALERT"
Control circuit
Flash Code 9
< 17VAC
* Flash code number corresponds to a number of LED fl ashes, followed by a pause and then
repeated. Trip and alert LED's fl ashing at same time means control circuit voltage is too low for
operation.
16
TROUBLESHOOTING - CONTINUED
Status LED Troubleshooting Information
Thermostat demand signal is intermittent
Low line voltage (contact utility if voltage at disconnect is low)
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Run capacitor has failed
Low line voltage (contact utitlity if voltage at disconnect is
low)
Check wiring connections
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Measure compressor oil level
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Compressor contactor has failed open
Check compressor contactor wiring and connectors
Check for compressor contactor failure (burned, pitted
or open)
Check wiring and connectors between supply and
compressor
— C
heck for low pilot voltage at compressor contactor coil
High pressure switch is open and requires manual reset
Open circuit in compressor supply wiring or connections
Unusually long compressor protector reset time due to extreme
ambient temperature
Compressor windings are damaged
Check compressor motor winding resistance
Run capacitor has failed
Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and the
compressor S terminal
Compressor start winding is damaged
Check compressor motor winding resistance
Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and the
compressor R terminal
Compressor run winding is damaged
Check compressor motor winding resistance
Compressor contactor has failed closed
Thermostat demand signal not connected to module
Control circuit transformer is overloaded
Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
Table 4. LED Diagnostics - Continued