Nordyne R-410A Installation And User Manual page 15

16 seer two stage r-410a split system
Table of Contents

Advertisement

Status
Status LED
LED
Description
Green
Module has
"POWER"
power
Thermostat
demand signal
Red "TRIP"
Y is present, but
compressor is not
running
Long Run Time
Yellow "ALERT"
Compressor is
Flash Code 1
running extremely
long run cycles
System
Pressure Trip
- Discharge or
Yellow "ALERT"
suction pressure
Flash Code 2
out of limits or
compressor
overloaded
TROUBLESHOOTING
Status LED Troubleshooting Information
Supply voltage is present at module terminals
Compressor protector is open
Check for high head pressure
Check compressor supply voltage
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Broken wire or connector is not making contact
Low pressure switch open if present in system
Compressor contactor has failed open
Low refrigerant charge
Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
Evaporator coil is frozen
Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator airfl ow (coil blockages or return airfi lter)
Check ductwork or registers for blockage
Faulty metering device
Check TXV bulb installation (size, location and contact)
Check if TXV/fi xed orifi ce is stuck closed or defective
Condenser coil is dirty
Liquid line restriction (fi lter drier blocked if present in system)
Thermostat is malfunctioning
Solenoid plug not connected
Y2 not wired at Comfort Alert
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)
Comfort Alert failure
High head pressure
Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system
Condenser coil poor air circulation (dirty, blocked, damaged)
Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
Return air duct has substantial leakage
If low pressure switch present in system, check Flash Code
1 information
Table 4. LED Diagnostics
15