7 Specifications

Environmental specifications

Specification
Temperature range
Operating
Non operating
Short-term
Wet bulb temperature
Operating
Non operating
Relative humidity (noncondensing)
Operating
Non-operating
1
All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m (1.8°F per 1000 ft) to 3048
m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1
psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (1 13°F). Altitude maximum for storage
corresponds to a pressure minimum of 70 KPa.

Rack specifications

1
Specification
U Height
Width
Depth
Cable Entry
Max Load
Rack Weight
Packaging and Pallet Weight
1
Including side panels.

Floor space requirements

Measurement
Front (appearance side) clearance
Rear (service side) clearance
Space between cabinets
Cabinet pitch
1
2
Minimum
in
36
36
--
--
Value
5°C to 40°C (41°F to 104°F)
-30°C to 60°C (-22°F to 140°F)
-5°C to 50°C (23°F to 122°F)
28ºC (82.4ºF)
38.7ºC (101.7ºF)
20% to 80%
5% to 95%
Value
36U
26.7 in (67.8 cm)
39.4 in (100.0 cm)
Top, Bottom
1200 lbs (544.3 kg)
500 lbs (226.8 kg)
485 lbs (219.9 kg) - R2 rack
200 lbs (90.7 kg)
Recommended
cm
in
91.4
51.2
91.4
51.2
--
< 1.0
--
27
Environmental specifications
cm
130
130
< 2.5
68.6
61