Bosch Plena Voice Alarm System Installation And Operation Manual page 37

Hide thumbs Also See for Plena Voice Alarm System:
Table of Contents

Advertisement

Plena Voice Alarm System
Power requirements
The system controller features a built-in 240 W power amplifier, able to drive up to 40
loudspeakers (6 W). Additional Plena Power Amplifiers are incorporated to provide additional
power, two-channel operation and spare amplification. To facilitate phased evacuation from
different floors of the hotel, guest areas are divided into separate zones, each fitted with 13
ceiling loudspeakers in the corridors. The bar uses cabinet loudspeakers, while the parking
garage uses weatherproof horn loudspeakers.
Layout
See Figure 3.17, Table 3.7 and Table 3.8
Zone
Z1
Z2
Z3
Z4
Z5
Z6
Z7-12
Table 3.7 Zones
Unit
LBB1990/00
LBB1992/00
LBB1996/00
LBB1997/00
LBB1956/00
LBB1957/00
LBB1935/00
LBB1938/00
PLN-DVDT
Table 3.8 Units
Figure 3.17 Example of a hotel
Bosch Security Systems B.V.
LBB1938/00
LBB1992/00
PLN-DVDT
LBB1990/00
LBB1997/00
Installation and Operation manual
Description
Bar
Restaurant
Lobby
Office
Kitchens
Parking garage
Floors 1 to 6
Total
Description
Controller
Router
Remote control
Remote control extension
Call station
Call station keypad
Power Amplifier (240 W)
Power Amplifier (480 W)
DVD Tuner
Z7-12
Z1-6
LBB1957/00
LBB1956/00
LBB1996/00
System overview | en
Power
3 x 6 W
6 x 6 W
2 x 6 W
1 x 6 W
2 x 6 W
3 x 10 W
78 x 6 W
582 W
No.
1 x
1 x
1 x
1 x
2 x
3 x
1 x
2 x
1 x
LBB1935/00
9922 141 1037x (V2.16) | V0.6 | 2011.09
37