142 en |
Clause / Requirement
f
13.2.2 The manufacturer shall prepare design
documentation that shall be submitted to the
testing authority together with the VACIE. This
documentation shall include drawings, parts
lists, block diagrams, circuit diagrams and a
functional description to such an extent that
compliance with this European Standard may be
checked and that a general assessment of the
mechanical and electrical design is made
possible.
13.3 Mechanical design requirements
13.3.1 The cabinet of the VACIE shall be of
robust construction consistent with the method
of installation recommended in the
documentation. It shall meet at least
classification IP30 of EN 60529:1991+A1:2000.
13.3.2 All interconnections and settings inside
the cabinet shall be accessible at level 3.
13.3.3 The VACIE may be housed in more than
one cabinet. If the documentation shows that the
cabinets may be installed in locations distributed
within the protected premises, then all of the
mandatory manual controls and indicators shall
be on one cabinet or on cabinets declared to be
only suitable for mounting adjacent to each
other.
13.3.4 All mandatory manual controls and light
emitting indicators shall be clearly labeled to
indicate their purpose. The labels shall be legible
at 0.8 m distance in an ambient light intensity
from 100 lux to 500 lux.
9922 141 1037x (V2.16) | V0.6 | 2011.09
maintenance information.
Installation and Operation manual
Compliance
Maintenance information of the Plena
Voice Alarm System is included in the IUI.
All of the mentioned design
documentation is available as TPD for
inspection by testing authorities.
Plena Voice Alarm System is compliant.
The installer is responsible for
implementing this requirement for 19"-
units, by means of using a correct 19"-
frame, meeting at least classification
IP30 of EN 60529:1991+A1:2000.
If the installer ensures that the physical
access to the Plena Voice Alarm System
is restricted to access level 3, all
interconnections and settings inside the
cabinet (e.g. interconnections between
the system elements) are accessible at
this access level.
The IUI shows that the Plena Voice Alarm
System cabinets may be installed in
locations distributed within the
premises. One dedicated Plena Voice
Alarm System remote control panels with
extentions as needed, can then be used
for all of the mandatory controls and
indicators. The installer is responsible for
proper installation in order to fulfill this
requirement.
All indicators are clearly labeled. For
language other than English. Permanent
labels are available.
Plena Voice Alarm System
Signature
Bosch Security Systems B.V.