Clause / Requirement
14.5.1 All executable code and data necessary to
comply with this European Standard shall be
held in memory that is capable of continuous,
unmaintained, reliable operation for a period of
at least 10 years.
14.5.2 For the program, the following
requirements shall apply:
a
b
14.5.3 For site-specific data, including
emergency message(s), the following
requirements shall apply:
a
b
c
d
Bosch Security Systems B.V.
the program shall be held in non-volatile
memory, which can only be written to at
access level 4, and
it shall be possible to identify the version
reference or references of the program at
access level 3. The version reference or
references shall be in accordance with the
documentation of 13.2.1.
the alteration of site specific data shall only
be possible at access level 3 or 4;
the alteration of site specific data shall not
affect the structure of the program;
if stored in read-write memory, there shall be
a mechanism which prevents the memory
being written to during normal operation at
access level 1 or 2, such that its contents are
protected during a failure in program
execution;
It shall be possible to either read or
interrogate the site specific data at access
level 2 or 3, or the site specific data shall be
given a version reference that shall be
updated when each set of alterations is
carried out.
Installation and Operation manual
Compliance
All Plena Voice Alarm System programs
(executable code and data) are stored in
Flash EEPROM.
Firmware (i.e. the program) can be
replaced using the File Transfer
Application. Using the File Transfer
Application requires access level 4.
The version of the firmware of the units is
visible on the units It is noted on the rear
of the unit (access level 3).
Alteration of configuration can only be
done via the configuration program or
access to the units from the rear. This
includes the File Transfer Application
(message sets). Getting access to the
configuration of the controller requires
access level 3. Using the File Transfer
Application requires access level 4.
Configuration of the Plena Voice Alarm
System is implemented to be data-driven
and is not part of the program
executable. Also transferring message
sets to the Plena Voice Alarm System is
data-driven and is not part of the
program executable. Therefore alteration
of the site specific data does not affect
the structure of the program.
Site specific data is stored in a Flash
EEPROM based file system. Writing of
data is only possible via the password
protected PC program.
Site specific data can be viewed and
maintained from the configuration (PC)
program. Using the configuration (PC)
program requires access level 3.
9922 141 1037x (V2.16) | V0.6 | 2011.09