NurseCall Main Unit
A.7
Connectors
A.7.1
LINE socket (unit bottom)
LINE socket
A.7.2
Power socket (unit bottom)
10V AC socket
A.7.3
RS-232 socket (unit rear)
RS-232 socket
The values in brackets are for the jumper setting for Paging. See Section Setting the jumpers
for Paging systems (except Medicall 800) and printers:, Page 18.
A.7.4
RS-485 socket (unit rear)
RS-485 socket
Bosch Security Systems
1 2 3 4 5 6
1 2 3 4
5
4
3
2
1
9
8 7
6
1 2 3 4 5 6
User Manual
Wiring
1. Flash Data GND
2. Not used
3. Not used
4. Not used
5. Not used
6. Flash Data IN/OUT
Wiring
1. Not used
2. AC-1 10-12VAC
3. AC-2
4. GND
Wiring
1. ---
2. TXD (RXD)
3. RXD (TXD)
4. ---
5. GND
6. ---
7. CTS
8. RTS
9. ---
Wiring
1. Relay output (a)
2. RS485 (A)
3. Termination = RS485 (A)
4. RS485(A) when jumper end line is placed
5. RS485 (B)
6. Relay Output (b)
F.01U.252.699 | V1.1 | 2012.01