LCD Configuration and Status
Changing the System Setup Options
Select System Setup from the Main Menu to enter the menu for changing system setup
options.
To change the system setup, you must enter the correct password. Use the Center and Enter
buttons to select the six digits for the password [0-9 and A-Z].
NOTE: The password must be six characters long. The default password is
change the password, refer to the section, "Setting the Password," in this chapter.
1. Select the first digit using the up and down arrow keys on the Center button.
2. Press the right arrow key on the Center button to move to the next digit.
3. To change a digit, use the left arrow key on the Center button to go back.
4. After entering the entire password, press the Enter button.
IMPORTANT: Record your password. After 30 minutes with no key presses, security is
automatically restored and the display changes to the main status display.
Setting the Baud Rate
Select Comm Setup from the System Setup menu to set up the baud rate for the
communication ports and option slots.
Table 3-8: Communications Setup Choices
LCD Display
Comm Setup
Serial Port x
Comm Setup
Opt-Slot x
3-12
Main Menu
System Setup
Enter Password
COMPAQ
System Setup
Comm Setup
Explanation
Select the communication port to set up. x is either 1 or 2.
Select the option slot to set up. x is either 1 or 2.
HP Uninterruptible Power System R12000 XR Models User Guide