Output Specifications; Overcurrent Protection - HP R1500 - UPS XR User Manual

Ups r12000 xr models user guide
Table of Contents

Advertisement

Specifications

Output Specifications

Table C-3: Output Specifications
UPS Model
R12000 XR WW
(worldwide)
Characteristics
Voltage
Output
Other features

Overcurrent Protection

A power distribution unit (PDU) provides overcurrent protection.
C-2
Effective VA
12000
Configuration
Setting (VAC)
The input voltage
range is 200-240 VAC
±20%.
Source of Power
Utility power
(normal range)
Battery power
Feature
Online efficiency
Voltage wave shape
Surge suppression
Noise filtering
HP Uninterruptible Power System R12000 XR Models User Guide
Nominal Power Rating
(W)
12000
Available Nominal
Output Voltage (VAC)
200, 208, 220, 230 or 240
Regulation
±3% of nominal output
voltage rating (within the
guidelines of the Computer
Business Equipment
Manufacturers Association)
±3% of nominal output
voltage rating
Specification
> 83%
Sine wave; 3% THD with
typical PFC load
High energy 6500 A peak
The input noise
suppression is comprised
of Normal Mode Filtering,
Common Mode Filtering, or
a combination of both.