Ups Shutdown (Via Rs-232C); Table 6.13 Remoteye Iii Monitored Parameters; Figure 6-11 Rs-232C Pin Assignments - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

Monitored Data
Operating Conditions
UPS Operating Status
(Described as "yes or "no")
Fault Details
(Described as "occurred" or "not occurred")
The DB9 connector pin assignment and female connector outline are shown in Figure 6-11.
Pin
I/O
Symbol
1
This pin is not used
2
Input
RXD
3
Output
TXD
4
Output
DTR
5
-
SG
6
Input
DSR
7
Output
RTS
8
Input
CTS
9
This pin is not used
6.7.1

UPS Shutdown (via RS-232C)

When the UPS is operating from its internal batteries, a 'shutdown' order can be sent to the UPS
instructing it to turn OFF after a user-specified amount of time.
This function can allows the user to stop discharging the UPS batteries after an orderly system
shutdown has been completed.
The UPS can be programmed to turn OFF up to 8 minutes after the 'shutdown' command is given.
This command can be cancelled before the specified time has elapsed by following the directions
listed on the RS-232C screen.
4200FA Installation and Operation Manual

Table 6.13 RemotEye III Monitored Parameters

Description
Receive Data
Transmit Data
Data Terminal Ready
Signal Ground
Data Set Ready
Request To Send
Clear To Send
Parameters
Input Voltage
Input Frequency
Battery Voltage
Utility Power OK
Low Battery Voltage Detected
UPS in BYPASS Mode
UPS in NORMAL Mode
Input and Output Frequency Synchronized
UPS FAULT Occurred
DC Bus Over-Current
DC Bus Over-Voltage
DC Bus Under-Voltage
Input Over-Current
Overheat
Overload Being Timed
Overload (allowable time exceeded)
Output Over-Voltage (during Normal Mode)
Output Under-Voltage (during Normal Mode)
DB9 Female connector outline
(facing connector)
5
4
3
9
8

Figure 6-11 RS-232C Pin Assignments

Output Voltage
Output Frequency
Output Current
2
1
7
6