Header Bar; Footer Bar; Table 9.4 Header Bar Components; Table 9.5 Footer Bar Components - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

9.8

Header Bar

The Header Bar on the graphic display panel displays three system parameters: the System Load,
Current Status, and System Time.
No.
System Load - Load per each phase as percent of full load. Low - Less than 10% Load.
1
Current Status - UPS status at the moment. (Status is delayed by a few seconds)
2
3
System Time - Current time in AM-PM format
9.9

Footer Bar

The Footer Bar on the graphic display panel displays three system parameters:
No.
Fault - Displays last fault sensed by UPS. A Fault causes the UPS to switch to bypass and it will
1
not automatically reset.
Warning - Displays last warning sensed by UPS. Multiple frequent warnings of the same type may
2
induce a fault condition.
3
UPS Mode - Selected operating mode.
68

Figure 9-5 Header Bar Detail

Table 9.4 Header Bar Components

Header Bar Components
Function

Figure 9-6 Footer Bar Detail

Table 9.5 Footer Bar Components

Footer Bar Components
Function
4200FA Installation and Operation Manual