Rs-232C; Ups Shutdown (Via Rs-232C) - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 80 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

4.2.2

RS-232C

The RS-232C serial communication interface is available via a DB9 female connector located
under the Remote Eye Cover on the front of the UPS (see Section 4 for location). This interface
allows control of the UPS from a personal computer running special TOSHIBA software. The
computer and the UPS are connected through a serial RS-232C communication port. The
available data from the UPS, via the RS-232C communication link is shown below.
Operating Conditions
UPS Operating Status
(Described as Yes or No)
Fault Details
(Described as Occurred or Not Occurred)
The connector pin assignment and female connector outline are illustrated below.
Pin
I/O
Symbol
1
This pin is not used
2
Input
RXD
3
Output
TXD
4
Output
DTR
5
-
6
Input
DSR
7
Output
RTS
8
Input
CTS
9
This pin is not used
4.2.3

UPS Shutdown (via RS-232C)

When the UPS is operating from its internal batteries, a Shutdown order can be sent to the
UPS telling it to turn OFF after a user-specified amount of time. This function can allow you to
stop discharging the UPS batteries after an orderly system shutdown has been completed.
The UPS can be programmed to turn OFF up to 8 minutes after the Shutdown command is
given. This command can be cancelled before the specified time has elapsed by following the
directions listed on the RS232 screen.
26
TOSHIBA
Description
Receive Data
Transmit Data
Data Terminal Ready
SG
Signal Ground
Data Set Ready
Request To Send
Clear To Send
Input Voltage
Output Voltage
Output Current
Battery Voltage
Input Frequency
Output Frequency
Utility Power OK
Low Battery Voltage Detected
UPS in BYPASS Mode
UPS in NORMAL Mode
Input and Output Frequency Synchronized
UPD FAULT Occurred
DC Bus Over-Current
DC Bus Over-Voltage
DC Bus Under-Voltage
Input Over-Current
Overheat
Overload Being Timed
Overload (allowable time exceeded)
Output Over-Voltage (during Normal Mode)
Output Under-Voltage (during Normal Mode)
DB9 Female connector outline
(facing connector)
5
4
9
3
2
1
8
7
6
4200FA User's Manual