Memory Capacity; Controller Status Led - Honeywell Spyder Specification Data

Programmable controllers
Table of Contents

Advertisement

SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
Universal Input (UI) Circuits
See Table 2 for the UI specifications:
Table 2. Universal Input Circuit Specifications.
Input
Sensor
Type
Type
Room/Zone
20K Ohm
Discharge Air
NTC
Outdoor Air
Temperature
Outdoor Air
C7031G
Temperature
C7041F
PT1000
(IEC751 3850)
TR23
500 Ohm
Setpoint
to
Potentiometer
10,500 Ohm
Resistive Input
Generic
Voltage
Transducer,
Input
Controller
Discrete Input
Dry Contact
closure
Counter/Meter
b
Pulse Input
a
C7031G and C7041F are recommended for use with these
controllers, due to improved resolution and accuracy when
compared to the PT1000.
b
One Universal Input (UI-1*) on the PUB1012S, PUB4024S,
PVB4022AS, and PVB4024NS is user selectable as a fast
digital pulse meter.
Hardware (PUB6438S, PUB6438SR,
PVB6436AS, and PVB6438NS)
CPU
Each controller uses a pair of microprocessors. The first is a
16-bit Texas Instruments MSP430 family microprocessor that
is used to manage the Inputs, Outputs and Control. The
second is a 32-bit ATMEL ARM 7 microprocessor that
manages communication for the Spyder BACnet.

Memory Capacity

Flash Memory: 372 kilobytes. The controller is able to retain
Flash memory settings for up to ten (10) years.
RAM: 72 kilobytes
63-1328—05
Operating
Range
-40° F to 199° F
(-40° C to 93° C)
-40° to 120°F
a
(-40° to 49°C)
-40° to 250°F
a
(-40° to 121°C)
-40° F to 199° F
(-40° C to 93° C)
-4° DDC to 4° DDC
(-8° DDF to 7° DDF)
or
50° F to 90° F
(10° C to 32° C)
100 Ohms
to
100K Ohms
0 - 10 Vdc
OpenCircuit ≥ 3000Ohms
ClosedCircuit < 3000Ohms
Max. frequency: 15 Hz
Min. pulse width: 20 ms
Hardware (PVB0000AS, PUB1012S,
PUB4024S, PVB4022AS, and
PVB4024NS)
CPU
Each controller uses a 32 bit ATMEL ARM 7 microprocessor.
Memory Capacity
Flash Memory: 512 kilobytes. The controller is able to retain
Flash memory settings for up to ten (10) years.
RAM: 128 kilobytes

Controller Status LED

The LED on the front of the controller provides a visual
indication of the status of the device. When the controller
receives power, the LED appears in one of the following
allowable states, as described in Table 3.
Table 3. Status LED States.
LED State
Blink Rate
OFF
not applicable
ON
ON steady;
not blinking
Very Slow
1 second ON,
Blink
1 second OFF
(continuous)
Slow Blink
0.5 second ON,
(continuous)
0.5 second OFF
Medium Blink
0.3 second ON,
(continuous)
0.3 second OFF
BACNET STATUS LED:
The LED on the front of the controller, between the BACnet
MS/TP terminals and MAC Address DIP Switches, provides a
visual indication of the BACnet MS/TP communication status.
When the controller receives power, the LED appears in one
of the following allowable states, as described in Table 4.
4
Status or Condition
No power to processor,
LED damaged, low voltage
to board, first second of
power up, or loader
damaged.
Processor not operating.
Application Program CRC
being checked. This takes
1-2 seconds and occurs on
each restart (power up,
reset and reflash, and
following configuration file
download).
Controller is operating
normally.
Controller alarm is active
or controller in process of
configuration file
download.
Controller is in reflash
mode or awaiting/receiving
reflash data via the
BACnet network.