Specifications - Honeywell Spyder Specification Data

Programmable controllers
Table of Contents

Advertisement

SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
DESCRIPTION
The programmable VAV/Unitary controllers are available in three models, as described in Table 1.
Controller
Programmable
Model
Type
PUB1012S
Unitary
PUB4024S
Unitary
PUB6438S
Unitary
PUB6438SR
Unitary
PVB0000AS
VAV
PVB4022AS
VAV
PVB4024NS
VAV
PVB6436AS
VAV
PVB6438NS
VAV
a
One Universal Input (UI-1*) is user selectable as a fast digital pulse meter
Each controller is programmable because the user chooses
which function blocks to use and how to connect them. It is
configurable because each Function Block has user-defined
behavior.
The PVB6436AS and PVB6438NS models are Variable Air
Volume (VAV) controllers, and the PUB6438S and
PUB6438SR models are Unitary controllers.
VAV Equipment Control
(PVB0000AS, PVB4022AS,
PVB4024NS, PVB6436AS, and
PVB6438NS)
The VAV controllers provide pressure-independent air flow
control and pressure-dependent damper control. VAV systems
generally provide cool air only to zones. However, each
controller has additional programmable inputs and outputs
that may be used to control devices, such as a fan or VAV box
reheat coils. Heaters can be staged electric or modulating hot
water. Supply and exhaust pressurization control are provided
on a zone basis.
Unitary Equipment Control
(PUB1012S, PUB4024S, PUB6438S,
and PUB6438SR)
Unitary equipment includes natural convection units, radiant
panels, unit heaters, unit ventilators, fan coil units, and heat
pumps. Unitary equipment does not require a central fan.
Depending on design, unitary equipment may perform one or
all of the functions of HVAC—ventilation, filtration, heating,
cooling, humidification and distribution. Unitary equipment
frequently requires a distribution system for steam or hot and
or chilled water.
63-1328—05
Table 1. Controller Configurations.
UI
DI
AO
(Universal
(Digital
(Analog
Input)
Input)
Output)
0
1
a
1
0
2
a
4
6
4
3
6
4
3
0
0
0
a
0
2
4
0
2
a
4
6
4
3
6
4
3
2
DO
(Digital
Velocity Pressure
Output)
Sensor (Microbridge)
2
NO
4
NO
8
NO
8 Relays NO
0
YES
2
YES
4
YES
6
YES
8
YES

SPECIFICATIONS

Electrical
Rated Voltage: 20-30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on model PVB6436AS)
Controller only Load: 5 VA maximum; models PVB6438NS,
PUB6438S, and PUB6438SR
Controller and Actuator Load: 9 VA maximum; model
PVB6436AS
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum
Environmental
VAV Operating & Storage Temperature Ambient Rating
(models PVB0000AS, PVB4022AS, PVB4024NS,
PVB6436AS, and PVB6438NS):
Minimum 32° F (0° C); Maximum 122° F (50° C)
Unitary Operating & Storage Temperature Ambient Rating
(models PUB1012S, PUB4024S, PUB6438S, and
PUB6438SR):
Minimum -40° F (-40° C); Maximum 150° F (65.5° C)
Relative Humidity: 5% to 95% non-condensing
Dimensions (H/W/D)
See Fig. 1 to Fig. 4 beginning on page 6 for dimensioned
drawings.
PUB1012S, PUB4024S, and PVB4024NS:6.25 x 4.81 x 2.26
in. (15.92 x 12.20 x 5.74 cm)
PUB0000AS, PUB4022AS (including Actuator):6.60 x 8.28
x 2.26 in. (16.70 x 21.10 x 5.74 cm)
PVB6436AS (including Actuator): 6.27 x 10.316 x 2.26 in.
(15.92 x 26.20 x 5.74 cm)
PVB6438NS: 5.76 x 6.85 x 2.26 in. (14.62 x 17.40 x 5.74 cm)
Series 60 Floating
Actuator
NO
NO
NO
NO
YES
YES
NO
YES
NO