Changing Chiller Plant Status Information
212
Figure 47. Failures Dialog Box
3. Click Reset All Failures.
A warning message displays (see Figure 48). This message explains
that all failed chillers will be re-inserted into the sequence.
Figure 48. System Failure Reset Warning
4. Click Yes to reset all failures.
IMPORTANT
This procedure will not reset any diagnostics at the chiller. It will only
return the chillers to the sequence.
5. Click Close to return to the System screen.
BMTX-SVU01B-EN