High limit safety cut-out

A high limit safety cut-out in the con-
sumer, e.g. the DHW cylinder, is
required when less than 40 litres cylinder
volume is available per m
area. This installation safely prevents
temperatures in excess of 95 °C in the
consumer.
Installation
Install the sensor of the high limit safety
cut-out inside the cylinder cap (Vitocell
300 accessory).
A
B Pump
Note
For the Vitocell 100, observe the max.
collector area that can be connected.