System Example 2 - Viessmann VITOSOLIC 200 Installation And Service Instructions Manual

Electronic temperature differential control unit
Table of Contents

Advertisement

System examples
System example 1
Required settings on the solar control unit
Main menu
Operator code
Solar options
■ System (see page 95)
Set solar values
■ Tcylset (set cylinder temperature)
■ ΔTon (start temperature differential for solar circuit
pump R1 eE)
■ ΔToff (stop temperature differential for solar circuit
pump R1 eE)
System options
■ Add. fct.
(Additional function for DHW heating)
For pump speed, see page 139.

System example 2

DHW heating with dual-mode DHW cylinder and central heating
backup with heating water buffer cylinder
Main components
■ Viessmann solar collectors
■ DHW cylinders Vitocell 100-B or
Vitocell 300-B
■ Heating water buffer cylinder
Vitocell 140-E or Vitocell 160-E
■ Vitosolic 200
■ Solar-Divicon
■ Solar pump line
■ Wall mounted oil/gas boiler or oil/gas
boiler
14
(cont.)
Delivered
condition
60 °C
Function description
DHW heating with solar energy
Solar circuit pump R1 eE starts and
DHW cylinder qP is heated up if the tem-
perature differential between collector
temperature sensor S1 eQ and cylinder
temperature sensor S2 qQ exceeds the
start temperature differential ΔT.
Solar circuit pump R1 eE is stopped in
accordance with the following criteria:
Setting
0000
0200
1
8.0 K
4.0 K
No
(if a DHW cir-
culation pump
is connected)
1
Yes